THEMA F
Installation and Servicing Instructions
Vue de la page 0
1 2 3 4 5 6 ... 27 28

Résumé du contenu

Page 1 - 01773 828400

1Heating and hot water for the professionals01773 828100IN WARRANTYTECHNICAL HELPLINE01773 828400THIS IS A CAT II2H3+ APPLIANCETHEMA FInstallation and

Page 2 - SERVICING SECTION

10BOILER INSTALLATIONStatutory requirementsThe installation of this boiler must be carried out bya competent person in accordance with the rel-evant r

Page 3 - DIMENSIONS

1123450mini2960255 miniREAR OUTLET FLUE INSTALLATIONB - Rear outlet side flueMark the horizontal centre line on the rear wall.Extend the horizontal ce

Page 4 - TECHNICAL DATA

12REAR OUTLET FLUE INSTALLATIONExtended flueThe horizontal flue is extended by using one or moreof the 1000 mm extension pipes, Saunier Duval partnumb

Page 5

13TOP OUTLET FLUE INSTALLATIONTop outlet flue - kit 86151 see diagram 18, is 1000 mm longand comprises:- Outer pipe...

Page 6 - THEMA F 23 E

14ELECTRICAL CONNECTIONWarning. This boiler must be earthedAll system components must be of an approvedtype.The mains electrical cable is supplied wit

Page 7 - FIXING JIG

15COMMISSIONINGImportant:- If this procedure is not carried out properly, the boilerwill go into safety lock-out until all of the air has beenpurged.-

Page 8 - PIPING SYSTEM INSTALLATION

16Des 044COMMISSIONINGOn reaching maximum temperature, the boilershould be turned off and the system drained asrapidly as possible whilst still hot.•

Page 9 - BOILER LOCATION

17SETTINGSCHANGING GAS TYPEGas valve settingAll boilers are tested and factory set during manu-facture. Should it be necessary to reset a gas valve,fo

Page 10 - REAR OUTLET FLUE INSTALLATION

18To ensure the continued efficient and safe opera-tion of the boiler it is recommended that it ischecked and serviced at regular intervals. The fre-q

Page 11

19REPLACEMENT OF PARTS• Undo and remove screw securing spark genera-tor to bracket and remove spark generator.• Fit replacement spark generator in rev

Page 12

2INSTALLATION AND SERVICING INSTRUCTIONSTHEMA F 23 E - THEMA F SB 18 E - THEMA F SB 23 ENote!The boiler serial number is marked on the label attached

Page 13 - TOP OUTLET FLUE INSTALLATION

20• Fit replacement PCB in reverse order to removal.Important: When fitting replacement PCB, ensurethat control knob spindles correctly locate into PC

Page 14 - ELECTRICAL CONNECTION

21REPLACEMENT OF PARTS• Push water valve back to disengage it from re-versing valve.• Unclip and remove loss of water pressure switchfrom left of reve

Page 15 - COMMISSIONING

22• Remove clip holding pipe to heat exchanger inrear of water valve. From front of boiler, grip clipwith long nosed pliers and pull upwards.• Unscrew

Page 16 - SAFETY DEVICES

23REPLACEMENT OF PARTSTo replace safety valve• Drain down entire heating system.• From below boiler, disconnect heating flow pipefrom rear of fixing j

Page 17 - SETTINGS

24REPLACEMENT OF PARTS• Unclip thermistor from pipe.• Pull off electrical cennections from thermistor.• Fit replacement thermistor in reverse order to

Page 18 - Diagram 28

25SCHEMATIC WIRING DIAGRAMSch 242IG - ON/OFF switchP - PumpSW3 - MicroswitchK4 - Hight limit thermostatK5 - Loss of water switchEV1 - Gas valve modula

Page 19 - REPLACEMENT OF PARTS

26FAULT FINDINGPrior to fault finding, check :Inlet gas pressure = 20 mbarElectrical supply = 240 V - 50 HzCentral heating system is pressurised at 1

Page 20

27FAULT FINDINGNO HOT WATERReplace main pcbRefer to chart n°2Check mains watersupply, water filterIs there at least 3 litres/minwater flow at tap ?Rem

Page 21

28108198 B 06/98

Page 22

3INTRODUCTIONThe THEMA F 23 E boiler is a wall mounted modulat-ing combination boiler with electronic ignition pro-viding central heating and instanta

Page 23

4Burner injector mm 1,20 1,20 1,20Inlet pressure mbar 20 20 20Diaphragme mm — — —Gas rate (maximum) m3/h 2,70 2,17 2,70Gas rate (minimum) m3/h 1,13 1,

Page 24

5Available pressure (kPa) between heatingflow and return(10 kPa = 1 m WG)1234550403020100500 100012354Flow rate through heating system (I/h)Pump :The

Page 25 - SCHEMATIC WIRING DIAGRAM

6BOILER SCHEMATICShy 131AB CDE45143171989101113121620216242223Diagram 43-Ignition module4-Heating temperature adjuster5-Hot water temperature adjuster

Page 26 - FAULT FINDING

7THEMA F 23 EFrom left to right, the fixing jig comprises:A - Heating return with isolating valve (m).B - Cold water inlet with isolating valve (p).C

Page 27 - SPARE PARTS

8HEATING SYSTEM DESIGNDiagram 6• The THEMA F boiler is compatible with any type ofinstallation.• Heating surfaces may consist of radiators, convec-tor

Page 28 - 108198 B 06/98

923450mini2960255 miniBOILER LOCATIONClearancesThe position of the boiler must be such that there isadequate space for servicing.The recommended clear